Fire rating

A fire-resistance rating typically means the duration for which a passive fire protection system can withstand a standard fire resistance test. This can be quantified simply as a measure of time, or it may entail a host of other criteria, involving other evidence of functionality or fitness for purpose.

Common rating systems

The following depict the most commonly used international time/temperature curves:

International fire-resistance ratings

For instance, in Germany, a fire door may have a "EI290-C" (former not. T90) designation, which means that the door has documented evidence of its ability to withstand that country's fire door test regime for a duration of 90 minutes.

There are many international variations for nearly countless types of products and systems, some with multiple test requirements.

Canada's Institute for Research in Construction (a part of the National Research Council and publisher of Canada's model building code - NBC) requires a special test regime for firestops for plastic pipe penetrants. Fire endurance tests for this application must be run under 50Pa positive furnace pressure in order to adequately simulate the effect of potential temperature differences between indoor and outdoor temperatures in Canada's winters. Special hoods are applied here to provide suction on the top side of a test assembly in order to reach the 50Pa pressure differential. Afterwards, a 30PSI hose-stream test may be applied.

Some fire doors in the North American Free Trade Agreement (NAFTA) area may even open up somewhat during a fire endurance test, although not too far, while a wall or floor assembly proper may not even be allowed an average temperature rise above 140°C or single point increases over 180°C.

Outdoor spray fireproofing methods that must be qualified to the hydrocarbon curve may be required to pass a host of environmental tests before any burn takes place, to minimize the likelihood that ordinary operational environments cannot render a vital system component useless before it ever encounters a fire.

If critical environmental conditions are not satisfied, an assembly may not be eligible for a fire-resistance rating.

Regardless of the complexity of any given test regime that may lead to a rating, the premise is generally product certification and, most importantly listing and approval use and compliance. Testing without certification and installations that cannot be matched with an appropriate certification listing, are not usually recognised by any Authority Having Jurisdiction (AHJ) unless it is in a realm where product certification is optional.

Tests for fire resistance of record protection equipment

The following classifications may be attained when testing in accordance with UL 72.

Class 100

This rating is the requirement in data safes and vault structures for protecting digital information on magnetic media or hard drives. Temperatures inside the protected chamber must be held below 125 °F (52 °C) for the time period specified, such as Class 125-2 Hour, with temperatures up to 2,000 °F (1,090 °C) outside the vault. The temperature reading is taken on the inside surfaces of the protective structure. Maintaining the temperature below 125°F. is critical because data is lost above that temperature threshold, even if the media or hard drives appear to be intact.

Class 150 Rating

This is the rating required to protect microfilm, microfiche, and other film-based information storage media. Above 150°F (65.5°C) film is distorted by the heat and information is lost. A Class 150-2 Hour vault must keep the temperature below 150°F. for at least two hours, with temperatures up to 2,000°F. (1,093.3°C) outside the vault.

Class 350 Rating

This rating is the requirement for protecting paper documents. Above 350°F (176.7°C) paper is distorted by the heat and information is lost. A Class 350-4 Hour vault must keep the temperature below 350°F. for at least four hours, with temperatures up to 2,000°F. (1,093.3°C) outside the vault.

Different time/temperature curves

Typically, most countries use the building elements curve, which is nearly identical in most countries as that is what results by burning wood. The building elements curve is characterized jointly by, including, but not limited to, DIN4102, BS476, ASTM E119, ULC-S101, etc. For exterior systems used in the petrochemical industry, the hydrocarbon curve is used. The only exposure beyond this, apart from the more recent tunnel curves shown above, would be the British "jetfire" exposure, which is not commonly used.

Big differences between different countries in terms of the use of the curves include the use of pipes, which shield the furnace thermocouples inside of NAFTA testing laboratories. This slows down the response time and results in a somewhat more conservative test regime in firestop.org treatise on the hose stream test.

Germany's DIN4102 also includes a significant impact test for a potential firewall, which is, however, applied from the wrong side: the cold side. Applying the impact from the cold side is more practical to do in a lab setting, however, potential impacts should come from the exposed side, not the unexposed side. Still, for the person designing, building and paying for the test, the fire resistance itself may be rather uneventful unless major problems appear. The burn itself is the long duration, up to 4 hours, but the hose stream test only lasts a few minutes, with large damage potential due to the sudden thermal and kinetic impacts, as the fire was upwards of 1,100°C (see curves above), whereas the sudden hose-stream test is as cold as the domestic water fed to the fire hose used in the test, which might be 10-20°C. This combined impact explains the debris that can be seen coming from test specimens during the hose stream test, as seen herein.

Because of the large differences in test regimes all over the world, even for identical products and systems, organizations that intend to market their products internationally are often required to run many tests in many countries. Even where test regimes are identical, countries are often reluctant to accept the test results and particularly the certification methods of other countries.

During a fire in a Rijkswaterstaat in particular, mandated an extremely tough standard, the curve of which is shown in the gallery above.

Example of a fire stop fire-resistance rating test

Construction of a test sample consists of a mock-up of a section of concrete floor, with typical mechanical and electrical utility components (pipes and cables) penetrating the floor assembly.A firestop mortar is applied around the penetrations.

The completed test sample is inserted into a furnace such that one side is exposed to a fire. The test is terminated when the fire stops successfully meet the test criteria in minimizing the amount of heat and smoke allowed to pass through the assembly, when the fire penetrates the fire stops. This determines the fire stop F-Rating. The length of time required for a penetrant or sample on average to exceed a specified average heat rise above ambient at any single location determines the duration for the FT Rating (Fire and Temperature). If a hose-stream test is passed afterwards, the rating can then be expressed as an FTH Rating (Fire, Temperature and Hose-stream). The lowest of the three determines the overall rating.











Example of a decking fire-resistance rating test

Testing of Decking Material that meet California Chapter 7A requirement for Ignition Resistant Material (IRM)

The construction of six test sample mock decks are made of the test material, three each are put through two separate tests designed to emulate the hazards of a natural forest fire. Part A: The Under Flame Test. This test consists of the mock decks being placed over a burner that produces a flame that can reach 10-12 inches over the sample deck. After three minutes the flame is extinguished, the sample deck must not a sustained flame at the consultation of the 40 minute test period. The test deck must also not show structural failure of any board and not have any falling particles that are still burning.






















Part B: The Burning Branding Test. This test consists of mock decks being subject the placement of a burning brand in the center of the mock deck to simulate the falling of burning embers during a wildfire. The deck must be absent of flame after the 40 minute test period and lack structural failure of any boards.

See also

External links

  • Efectis
  • BAM Berlin
  • Underwriters Laboratories
  • Underwriters' Laboratories of Canada
  • Institute for Research in Construction/NRC
  • iBMB TU Braunschweig)
  • Gütegemeinschaft Brandschutz im Ausbau
This article was sourced from Creative Commons Attribution-ShareAlike License; additional terms may apply. World Heritage Encyclopedia content is assembled from numerous content providers, Open Access Publishing, and in compliance with The Fair Access to Science and Technology Research Act (FASTR), Wikimedia Foundation, Inc., Public Library of Science, The Encyclopedia of Life, Open Book Publishers (OBP), PubMed, U.S. National Library of Medicine, National Center for Biotechnology Information, U.S. National Library of Medicine, National Institutes of Health (NIH), U.S. Department of Health & Human Services, and USA.gov, which sources content from all federal, state, local, tribal, and territorial government publication portals (.gov, .mil, .edu). Funding for USA.gov and content contributors is made possible from the U.S. Congress, E-Government Act of 2002.
 